WebJul 26, 2024 · Karma: 13. Rank: Padawan. For anaolog Scaling, particulary a Analog value, you will need to use two instructions. Norm_X and Scale_X. Normalize the raw input value and then scale it to desired range. WebWe will first calculate the linear scaling for the fill height or f. I’m going to skip a few steps since we covered this in the first section. y = f = 2x, where x is the voltage output of the …
Analog Circuits Training - Analog Scaling using y=mx+b
WebApr 15, 2002 · I have seen a post by Terry Woods giving the general formula below: Y1 + (Y2 - Y1)* (X - X1)/X2-X1 =Y. If my analogue input gets values from 0 to 32000 and I want a … WebSep 29, 2007 · So scaling a 4-20mA input to a -1 to 0 bar output would be fitting a line to the following points. (4, -1) and (20,0). You could plug in the values to y=mx+b and solve for m and b. Or, m= (y2-y1)/ (x2-x1) then plug in either set of x,y values to get b. You should plug in the other set to check your equation. iottie 5 phone holder
How to scale Analog Input values - Siemens PLC
Web2013 - 2024. MEng Electrical and Mechanical Engineering student currently in my 5th year, taking relevant courses in Solid Mechanics, Control Systems, Thermodynamics, Power … WebThe measured value is converted by the sensor into an electrical signal whose current strength is set between 4 and 20 mA depending on the measured value. If the measured value is at the lower end of its scale, for example 0 bar, the signal is set to 4 mA. If the measured value is at the upper end, perhaps 10 bar, then the signal from the ... WebMay 16, 2007 · How to scale the analog values in siemens s7 400 LIVE PLC Questions And Answers on which basis major load is selected